The KDP210V is a versatile Air Differential Pressure transmitter fully scalable between –2000Pa to +2000Pa with selectable units with backlight LCD, the product is ideal for monitoring and controlling differential pressure in ventilation systems.
Supplied complete with tube connection kit.
Specification
Range:Â Â Â Â Â Â Â Â Â Â Â Â Â -2000Pa to +2000Pa
Overpressure:Â Â Â Â Â X15
Units:                Pa, kPa, hPa, daPa, mbar, mmHg,  mmH2O, inHg
Output:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 0-10V, 0-5V
Supply Voltage:Â Â Â Â 18-30Vdc
Accuracy:           < ± 1% FS @ 05 to +65°C
Response Time:Â Â Â Â Â 0.1s, 0.5s, 1s, 2s
Termination:           Rising clamp for 0.5 to 2.5mm² cable.
Media:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Air and neutral gases
Operating temp:    -20 to +80°C
Power:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â < 3 Watts
Protection:Â Â Â Â Â Â Â Â Â Â Â IP65
Datasheet
KDP210V