Tridium’s Niagara Edge 10 is an IP-based field equipment controller powered by the Niagara Framework®. Niagara Edge 10 controllers drive applications such as zone temperature control, and the operation of fan coil units, single-stage air handling units, water-source heat pumps and more. Niagara Edge 10 controllers run the full Niagara stack, with 10 points of on-board IO and IO-R expansion capability. Niagara Edge 10 licensing supports three devices and 50 total points to harness the full power of Niagara at the edge.
Point options available: 50 | 100 | 150 | 250 | 300 | 500 | 1250
ACE DETERMINISTIC ENGINE
• Utilise Wire Sheet to create deterministic applications that enable fast startup to control time and deterministic timing when servicing the IO.
NETWORK
• Edge 10 controllers can be daisy-chained to continue network connectivity and eliminate the need for separate wiring back to a switch
• Connect Niagara Edge 10 controllers to your main building or IT network and manage them directly with a Supervisor alongside a JACE®
• Use the secondary Ethernet port of the JACE 8000 to create a private network of Niagara Edge 10 controllers
AGENCY CERTIFICATIONS
• FCC Part 15, class B
• C-UL • CE • UL916, Open Energy Management Class 2
• RoHS2
• REACH
• WEEE
• CAN/CSA-C22.2 No. 205-12
Tridium_Niagara_Edge10_features_Documents
Tridium_Niagara_Edge10_FAQs_Documents
Tridium_Niagara_Edge10_doc_Startup_Documents
Tridium_Niagara_Edge10_Datasheet_Documents
The Niagara versions available for this controller in the latest Installer version:
- Niagara 4.4.73 (not recommended)
- Niagara 4.4.92 (not recommended)
- Niagara 4.6.96.28 (Use the installer v1.9)
- Niagara 4.7.109.20 (Use the installer v1.9)
- Niagara 4.8.0.110 (Use the installer v1.9)
- Niagara 4.9.0.198 (Use the installer v1.4)
- Niagara 4.9.1.30 (Use the installer v1.9)
- Niagara 4.10.0.154(Use the installer v1.5)
- Niagara 4.10.1.36(Use the installer v1.7)
- Niagara 4.10.3.20 (Use the installer v1.9)
- Niagara 4.11.1.16 (Use the installer v1.9)
- Niagara 4.12.0.156 (Use the installer v1.8)
- Niagara 4.12.2.16 (Use the installer v1.9)
- Niagara 4.10.7.42.1
- Niagara 4.10.9.14.1
- Niagara 4.13.2.18
- Niagara 4.14.0.162
- Niagara 4.14.2.12
- Niagara 4.15.1.16
- Niagara 4.15.2.38
What is the device’s default IP address?
The fallback static IP is built using the last four digits of the device’s serial number.
The route and subnet mask are set appropriately.
Static IP: 192.168.1xx.xx where xx.xx are numbers lifted from the serial number, as shown in the following two examples: –
For serial number: 010106, the resulting IP is: 192.168.101.06 –
For serial number: 106, the resulting IP is: 192.168.101.06
Route: 192.168.1.1
The default subnet mask is: 255.255.0.0
What are the default platform Credentials?
The default credentials are the same as for all the Tridium controllers:
User: tridium
Password:niagara
What communication networks are available?
In this stage, the Networks that work are:
– Modbus RS-485
– Modbus TCP
– BACnet TCP
– BACnet MSTP is available for versions N4.6 and N4.7.
– Niagara Network
What features are implemented into this controller compared to the Tridium Jace?
The Edge 10 has the same features as a Tridium N4 controller:
-Alarm
-Histories
-PX pages (web User Interface pages), HTML 5 web viewing
-Communication with Niagara controllers and Supervisors through the Niagara Network