The GLD gas leak detection range is suitable for use in Boiler Rooms and other Commercial applications, providing safety and shut-down functions in the event of gas leakage. Control units are available in 1, 2 or 3 channels for connection to 1, 2 or 3 remote sensors. They are mounted in DIN rail housings, with the option of panel- or wall-mount enclosures. Output relays to operate auxiliary devices such as Solenoid Gas Valves or Sirens, and fault remote signalling are fitted to all units. Power supply is 230VAC or 12-24VDC, and sensors are available for Natural Gas, LPG/Propane, and Carbon Monoxide.
Specification
Power Supply:           GLD361: 230Vac ± 10% @ 50Hz GLD65*: 12V ± 10%
Power Consumption:Â Â Â GLD361: 3VA GLD65*: 7VA
Relay Outputs:Â Â Â Â Â Â Â Â Â Â Â GLD361: 5(1)A @ 250V SPDTÂ GLD65*: 2 x 5(1)A @ 250V SPDT
Pre-alarm Thresholds…
Natural Gas:Â Â Â Â Â Â Â Â Â Â Â Â Â Â 0.3% to 0.8% (3000 to 8000ppm)
LPG:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 0.14% to 0.35% (1400 to 3500ppm)
CO:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 0.012% to 0.03% (120 to 300ppm)
Alarm Thresholds…
Natural Gas:Â Â Â Â Â Â Â Â Â Â Â Â Â Â 0.5% to 1.25% (5000 to 12500ppm)
LPG:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 0.22% to 0.56% (2200 to 5600ppm)
CO:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 0.02% to 0.05% (200 to 500ppm)
Sensors…
Natural Gas:Â Â Â Â Â Â Â Â Â Â Â Â Â Â GLD150
LPG:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â GLD250
CO:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â GLD350
Materials:                 Base – Nylon, Cover – ABS
Ambient…
Storage:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â -25ËšC to +60ËšC
Operating:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 0ËšC to +45ËšC