CO² transmitters can be used in a broad range of applications including air quality monitoring in buildings. CO² concentration levels in buildings are monitored to provide an indication of occupancy and to drive a ventilation control strategy. An effective DCV (Demand Controlled Ventilation) strategy will conserve energy and maintain indoor air quality.
Specification
Measurement Range:Â Â Â Â Â Â Â Â 0-2000 PPM factory calibrated
Duct Air Velocity:Â Â Â Â Â Â Â Â Â Â Â Â 0 to 450 meter/min
Temp Dependence:Â Â Â Â Â Â Â Â Â Â Â 0.2% of full scale per ËšC
Stability:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â < 2% of full scale over the life of the sensor (15 years typical).
Accuracy:                     ± 40ppm +3% of reading @ 22˚C (72ºF) when compared with a factory-certified reference.
Non-linearity:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â < 1% of full scale @ 22ËšC (72ËšF)
Pressure Dependence:Â Â Â Â Â Â Â 0.13% of reading per mm of mercury
Calibration:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Sensors will be calibrated at zero and spanned at the factory. Calibration in the field will not be required. Sensors will ship with ABC Logicâ„¢ enabled.
Response Time:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Three minutes is typical for a 90% step change at low duct speeds.
Sampling Rate:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Every two seconds, 25% duty cycle
Warm-up Time:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â < two minutes (operational); 10 minutes to achieve maximum accuracy.
Operating Conditions…
Temperature:                 0…50˚C
Humidity:                     0…95% RH, non-condensing
Storage Conditions:          -20˚C…70˚C
Output:                        0…10Vdc
Power Supply:                18…30Vac, 50/60Hz or 18…42Vdc
Dimensions…
Probe Length:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 10.46cm
Probe Diam:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 3.14cm
Junction Box Depth:Â Â Â Â Â Â Â Â Â Â 4.06cm
Height:Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 7.62cm











Reviews
There are no reviews yet.