HVAC Products

,

Static Positive Pressure Switch Bailey & Mackey

Price range: £103.00 through £126.00

Please select the required pressure range from below

- +

⚡ Electrical Calculator


🔌 Cable Size Reference


🌬 Unit Converter


🔋 Transformer VA & MCB Calculator


📊 Reference Guide

Current (A) Cable Size (mm²)
6 1
6-12 1.5
12-25 2.5
25-32 4
32-40 6
40-64 10
You must consider Ambient Temperature, Location and Thermal insulation in contact with cable.

Description

This series of pressure switches can be used for all applications where an electrical circuit must close or open at a specified pressure. The robustness of this series of pressure switches ensures that all applications across all industries can be met.

 Robust & Reliable  Diaphragm Operated  Proven Performance  Enclosure Rating IP65  Twin Circuit Option  CE Marked  LPCB Approved  Fully Adjustable  Wetted Parts for use with most fluids  Easily Customised

Standard Materials
Diaphragm: Beryllium Copper
Seal: Glass-filled PTFE ≤11 Bar Nitrile Rubber >11 Bar
Housing: Aluminium/Zinc Diecast
Cover: Glass-filled nylon with Neoprene seal
Base: Brass

Set Point Accuracy: +/- 2%
Temperature Range: -10 to +85°C (Process fluid must not solidify)
Temperature Coefficient: 0.05% (of range per 0°C from 20°C)

Electrical Ratings
10 Amp at 250V ac 50Hz Inductive Load
1 Amp at 30V dc Inductive Load
For other voltages and currents, please consult our Technical Sales Department.

Maximum Pressure
To ensure long service and life, select the pressure range as follows:
Dynamic pressure applications Pmax = 75% of Range
Static pressure applications Pmax = 100% of Range
The maximum pressure that can be applied is 125% of the pressure range

Installation
The Switches can be mounted directly on the connecting thread. Sealing grooves are machined into the end face of the parallel threads for the use with sealing washers. A mounting bracket is available if required.

Vacuum Setting
At ambient pressure, the switches will be in the operated condition; consequently, the wiring should be reversed, i.e., NO becomes NC.

Connecting Threads
All Connecting threads used in industry are available, including British, American and metric. Please state the required connection thread when ordering.
Flanged fittings are available, and most types of Hygienic fittings can be supplied assembled directly onto the Pressure Switch. If flush diaphragms are required, please consult our Technical Sales Department.
Alternative Wetted Parts are also available. Please contact our Technical Sales Department for options and information on this.

Manual

Datasheet Static Positive Pressure Switch 1381-2381-2

Business & Industrial > Automation Control Components

Additional information

Weight 0.39 kg
Dimensions 16 × 11 × 6 cm
Pressure

-1-1 Bar, 0.2-4 Bar, 0.5-11 Bar, 0.7-14 Bar, 2-28 Bar, 2-42 Bar, 5-125 MBar, 15-250 MBar, 25-400MBar